This unit uses a high stability Electro-chemical sensor with built in temperature compensation and a programmable display
for controlling the concentration of oxygen in an enclosed compartment.
Day to day calibration is carried out from the display panel. All the calibration and alarm parameters are retained in non volatile memory.
Principle of Operation
Oxygen concentration is sensed and displayed on the controller, a programmable set point is used to select the required Oxygen level.
If the Oxygen concentration sensed by the fuel cell is below the control set point value, the controller will operate the
solenoid valve for a user defined time period in the range 0 to 255 seconds. After the injection period the solenoid valve
will close for a further user defined time period in the range 0 to 255 seconds, to allow for mixing. If the Oxygen level is
still below the control set point the cycle repeats until the required Oxygen is reached.
Specifications
Operating Principles : Electro-chemical
Range : 0 to 100% Oxygen
Accuracy : 1% of Full Scale
Response Time : 90% in 12 Seconds
Relay Output : 8 Amp change-over relay
Warranty : 12 months ( sensor 9 months )
Power Requirements : 110, 220 VAC or 24 VDC 6 W
Optional Extras : O2 Clean, Solenoid valve
Dimensions
Height = 128 mm
Width = 106 mm
Depth = 218 mm
|